SPECIFICATIONS
MODEL VM4302
TWO CHANNEL DIFFERENTIAL AC VOLTAGE MONITOR |
|
The Model VM4302 voltage monitor is a highly stable two channel differential AC voltage monitor. Each channel is completely independent from the other. The below specifications apply to both channels. |
| Frequency Range: |
400Hz to 5000Hz |
Input Voltage Ranges:
Range 1:
Range 2:
Range 3:
Range 4:
Dial Accuracy: |
5 to 10VRMS
10 to 20VRMS
20 to 40VRMS
40 to 80VRMS
+/-1% |
Sensitivity Switch:
Position 1:
Position 2:
Position 3:
Position 4:
Position 5:
Position 6:
Position 7:
Position 8: |
+/-0.01% full scale
+/-0.02% full scale
+/-0.05% full scale
+/-0.1% full scale
+/-0.2% full scale
+/-0.5% full scale
+/-1.0% full scale
+/-10% full scale |
Voltage Monitor Stability:
Vs Time:
Vs Line:
Vs Temp: |
+/-0.01%/week under constant conditions.
+/-0.001% for +/-10V line
+/-0.001%/deg C, 15 to 40 deg C. |
| Input Configuration: |
Two wire isolated. Each channel is available separately. |
| Waveshape: |
Sine |
| Sensing Mode: |
Average sensing |
| Auxiliary Recorder Output: |
+/-1V full scale. Output impedance is 1.9Kohm +/-1%. Will deliver +/-0.5ma into 100 ohms. |
| Input Power: |
115V +/-10V, 50/60 Hz (or 220/230/240 VAC) |
   |